2019.04.23.2_ts_pirwp34

Firmware status

CE-certified and ready for commercial use.

What's new

  • Occupancy mode
  • Heart-beat support

Default functionality

  • report an indicative count of detected movements every 1 minute
  • report battery-level information every 1 minute
  • The device blinks led (red) once when starting up

Thingsee Messages

Following Thingsee Message profiles are used

* Thingsee Message common profile (1)

  • 1101 Thing information request
  • 1102 Thing information unavailable response
  • 1100 Thing system info data
  • 1110 Thing battery info data
  • 1111 Thing orientation data
  • 1202 Sensor network neighbouring data
  • 1312 Firmware binary version info
  • 2100 Occupancy info data

* Thingsee Message presence profile (13)

  • 13100 presence count

Example data as received from Thingsee Operations Cloud

Movement info

[{
    "tsmId"        : 13100,
    "tsmEv"        : 10,
    "tsmTs"        : 1492603998,
    "tsmTuid"      : "TSTF02S3R1AL",
    "tsmGw"        : "TSGW1234",
    "moveCount"    : 16
}]

moveCount is an indicative value of detected movements during the measurement period.

Occupancy info (when enabled)

[{
    "tsmId"        : 13100,
    "tsmEv"        : 10,
    "tsmTs"        : 1492603998,
    "tsmTuid"      : "TSTF02S3R1AL",
    "tsmGw"        : "TSGW1234",
    "state"        : 1
}]

state is current occupancy state. Value '0' means sensor area is not occupied and value '1' means area is occupied.

The firmware implements occupancy analytics as follows.

UserUserThingseePRESENCEThingseePRESENCECloudCloudUser enters, leaves or stays at sensor detection areastate = moveCount > 0 ? true : falsealt[state is changed]Send tsmId 2100reset timer[state is not changed]check if timer expiredalt[2h timer expired]Send tsmId 2100reset timer[timer not expired]do nothing

  • Interval is set as default to 60s and can be remotely changed over Thingsee Services API.

Performance

  • measurement range: as described in installation notes
  • battery-life (interval): 3 years (1min)

A heat source shape, size, movement, and temperature may affect the performance. The heat source must move for accurate detection.

Factory configuration

The following parameters are configured during the manufacturing process.

  • Wirepas connectivity parameters

Remote configuration

The following parameters are configurable remotely over Thingsee Operations Cloud.

  • measurement interval
  • enable/disable Thingsee positioning anchor mode
  • enable/disable occupancy mode
  • Wirepas head-node and sub-node configuration

Installation Notes

Detecting capability

Sensitivity cone is roughly 100 degrees in horizontally and vertically up to 2.5 meters. From 2.5m to 5m vertical direction is limited.

Area blocking